Smart Pressure Transmitter
TTC SMART PRESSURE
TRANSMITTER LAB #X
HONEYWELL ST3000
OBJECTIVES
1. Introduce
smart temperature transmitters and smart field communicator functions and
operations.
2. Calculate
and validate smart temperature transmitter output responses.
3. Configure
the smart temperature transmitter for both thermocouple and RTD sensors.
4. Perform
a 4-20 mA trim (i.e. "D to A" calibration) on a smart temperature
transmitter.
5. Calibrate
the input section (i.e. "A to D" calibration) of a smart temperature
transmitter.
6. Perform
a cloning procedure.
EQUIPMENT
-
Honeywell ST3000 Smart Pressure Transmitter - 250 Ohm Resistor
- Honeywell Smart Field Communicator - 24 Volt Power Supply
-
Druck 605 DPI (Digital Pressure Indicator) - Fluke 8060A DMM
PRE-LAB
1.
Explain the difference between a
smart pressure transmitter and a conventional pressure transmitter.
2. Explain what is meant by “configuring” a smart pressure transmitter versus
"calibrating" a smart pressure transmitter.
PROCEDURE
1. Connect the Honeywell ST3000 Smart Pressure
Transmitter to the bench 24 volt power supply. Include in the loop a 250 resistor
(necessary for digital communication) and a Fluke DMM. Connect the Honeywell Smart Field
Communicator (SFC) to the transmitter's 4-20 mA measurement loop
terminals: red to positive and black to
negative. Refer to the drawing shown
below:
2. Connect
the Druck 605 DPI pressure source to the high (H) side of the transmitter,
making sure connections are tight.
3. Configure
the ST3000 Smart Pressure Transmitter for the following:
Damping Time = 1.12
seconds
Units = “
W.C.
Lower Range Value = 0
“
W.C.
Upper Range Value = 100
”
W.C.
Output =
linear
The
first thing that you must do is transfer the transmitter's configuration
information into the Working Memory of the SFC.. To do this, turn the SFC on, then press the [ID]
key.
The
display will look similar to the one shown below:
To
adjust the damping time, follow the procedure on page 53 of the STS103
operating guide.
To
adjust the units in which to display values, follow the procedure on page
54 of the STS103 operating guide.
To
key in the LRV and URV, follow the procedure on pages 58 and 59
of the STS103 operating guide.
3. (continued)
For
the previous elements, any changes that you make to the Working Memory of the
SFC are also made (sent) to the Working Memory of the transmitter.
The
remaining element (output info) is only accessible in the configuration
mode. To activate this mode, press [CONF],
then press [ENTER]. Then follow
the procedure on pages 62 and 63 of the STS103 operating guide to change the output
type to linear.
Note,
in configuration mode, after you have changed the above elements as required,
these changes are only made to the SFC Working Memory. In order to make changes to the actual
transmitter (XMTR) Working Memory, the SFC Working Memory must be transferred
to the XMTR Working Memory. Follow the
procedure carefully.
Note,
after transferring the SFC memory to the XMTR memory, check the LRV and URV to
see if they are still correct (sometimes these values will change if the probe
type is changed!). Correct if necessary.
4. Quickly verify the configuration by
measuring the pressures indicated in table 1. Record all required information
in table 1. (Note, reference pressure
measurement is the pressure as indicated by the Druck 605 DPI pressure source.)
Note,
it is possible to display the pressure (as measured by the transmitter) on the
SFC display. Press [SHIFT], then
press [INPUT]. Pressure is
updated once every 6 seconds.
Note,
it is possible to display the transmitter output on the SFC display. Press [OUTPUT]. Transmitter output is updated once every 6
seconds.
Note,
for table 1, pressure is to be calculated based on the mA signal as measured
and indicated by the DMM.
5. With
Honeywell Smart Transmitters, it is possible to perform a 4-20 mA trim (i.e.
"D to A" calibration). If
this procedure is to be performed, it is important that the transmitter output
be measured with a very accurate ammeter. We will use the Fluke 8060A to measure the
current output ... however, a more accurate meter should be used!
Prior
to performing this calibration, record the current as indicated by the Fluke at
0%, 25%, 50%, 75% and 100%. Record your
observations in table 3. Follow the
procedure "Using a Smart Transmitter as a Current Source" on pages 43
and 44 of the STS103 operating guide.
To
do a DAC calibration, follow the procedure on pages 64 to 66 of the STS103
operating guide.
After
performing the DAC calibration, record the current as indicated by the Fluke at
0%, 25%, 50%, 75% and 100%. Record your
observations in table 3. Follow the
procedure "Using a Smart Transmitter as a Current Source" on pages 43
and 44 of the STS103 operating guide.
6. With
Honeywell Smart Transmitters, it is also possible to calibrate the input
section of the transmitter (i.e. "A to D" calibration). If this procedure is to be performed, it is
important that the transmitter input be simulated with a very accurate
device. In this step, we will use a Druck 605 DPI as the pressure source
... however, a more accurate device should be used!
Prior
to performing the sensor trim, ensure that the transmitter is still configured
for a pressure range of 0 psig to 100 “W.C.
(keypad method), then record the pressure as indicated by the Honeywell
communicator (press [SHIFT], then press [INPUT]) when
simulating pressures of 0 “
W.C., 25 “
W.C., 50 “ W.C., 75 “
W.C. and 100 “ W.C..
Record your observations in table 3.
Honeywell
has chosen not to show the user how to perform an ADC calibration in it’s STS103 manual. The procedure is summarized below (two point
calibration):
(a) Simulate
0 “
W.C. with the Druck 605 DPI, then press [LRV] key, display should
indicate 0 “
W.C., then press [CORRECT] key, then press [YES] key. The display should now say "LRV
CORRECTED", the transmitter output should be exactly 4 mA, and the
displayed pressure (as indicated by the Honeywell communicator) should be
exactly 0 “
W.C. (press [SHIFT], then press [INPUT]).
(b) Simulate
100 “ W.C. with the Druck 605 DPI, then
press [URV] key, display should indicate 100 “
W.C., then press [CORRECT] key, then press [YES] key. The display should now say "URV
CORRECTED", the transmitter output should be exactly 20 mA, and the
displayed pressure (as indicated by the Honeywell communicator) should be
exactly 100 “ W.C. (press [SHIFT], then
press [INPUT]).
After
performing the ADC calibration, record the pressure as indicated by the
Honeywell communicator (press [SHIFT], then press [INPUT]) when
simulating pressures of 0 “
W.C., 25 “
W.C., 50 “ W.C., 75 “
W.C. and 100 “ W.C..
Record your observations in table 3.
7. Now that you have performed a 4-20 mA
trim and a sensor trim, repeat step 4.
Record all required information in table 4. You should find that you now have less error
due to the "trims".
Note,
again, pressure is to be calculated based on the mA signal as measured and
indicated by the DMM.
8. Rerange the ST3000 by using the applied
pressure input source method and the STS103 SFC (page 60 and 61 of the STS103
operating guide). The required pressure
range is 5 to 20 kPa. Use the
Druck 605 DPI as the pressure source.
Please note that, after reranging
with the pressure input source method, it is possible that that the 4 to 20 mA output
signal will correspond correctly with the pressure source, yet the pressure as
indicated by the STS103 SFC displays a slightly different value than the
pressure source. Since you have
performed a sensor trim prior to reranging with the pressure input source
method, the above stated condition should not exist.
9. After reranging using the pressure
input source method, quickly verify the configuration by measuring the
pressures indicated in table 5. Record all required information in table
5. (Note, reference pressure measurement
is the pressure as indicated by the Druck 605 DPI.)
Note,
for table 5, pressure is to be calculated based on the mA signal as measured
and indicated by the DMM.
10. Using the "RESET CORRECTS" , return
the Honeywell ST3000 Smart Pressure Transmitter to it's factory
calibration. The procedure is outlined on page 38 of the STS103
operating guide.
11. The Hold Memory of the SFC can be used
for cloning, i.e. downloading information from one transmitter and uploading
the same information to a number of others.
The Hold Memory is also useful for replacing a damaged transmitter with
a spare.
Perform
a cloning procedure as follows:
(a) Copy
the transmitter data base into the SFC Hold Memory by pressing the [SAVE]
key, then [ENTER] key.
(b) Copy
the contents of the SFC Hold Memory back into the same transmitter (normally
not the same transmitter) by pressing the
[RE-STORE]
key, then [ENTER] key.
12. With
Honeywell smart transmitters, when changes are made to the transmitter
configuration and calibration, these changes are only made to the Working
Memory of the transmitter. Prior to
disconnecting the SFC from the transmitter, it is necessary to tell the
transmitter to store all of the changes into the transmitters non-volatile
memory. Update the non-volatile memory
by pressing the [SHIFT] key, then [NON-VOL] key.
TTC RESULTS LAB #X
NAME: _______________________________ DATE: __________________
LAB
PARTNER:
_____________________________ CLASS:
_________________
Pre-Lab
Signature: ________________________
Difference between a smart pressure
transmitter and a conventional analog pressure transmitter (pre-lab Q#1):
What
is meant by "configuring" versus "calibrating" (pre-lab
Q#2):
Completion of table 1 (keypad method)(step 4):
Input
(“ W. C.)
|
Measured Loop
Current
(DMM, mA)
|
Smart
Tx Pressure (“
W.C.)
|
Error
(“ W.C)
|
0.00
|
|||
25.00
|
|||
50.00
|
|||
75.00
|
|||
100.00
|
Table
1
Note,
for table 1, pressure is to be calculated based on the mA signal as measured
and indicated by the DMM.
"D to A" calibration (step
5):
Before
|
After
|
||||
Output
Setting (%)
|
Expected
Current (mA)
|
Actual
Current (mA)
|
Output
Setting (%)
|
Expected
Current (mA)
|
Actual
Current (mA)
|
0
|
4
|
0
|
4
|
||
25
|
8
|
25
|
8
|
||
50
|
12
|
50
|
12
|
||
75
|
16
|
75
|
16
|
||
100
|
20
|
100
|
20
|
Table
2
"A to D" calibration (step
6):
Before
|
After
|
||||
Simulated
Input Setting
(“ W.C.)
|
Expected
Pressure Display
(“ W.C.)
|
Actual
Pressure Display
(“ W.C.)
|
Simulated
Input Setting
(“ W.C.)
|
Expected
Pressure Display
(“ W.C.)
|
Actual
Pressure Display
(“ W.C.)
|
0
|
0
|
0
|
0
|
||
25
|
25
|
25
|
25
|
||
50
|
50
|
50
|
50
|
||
75
|
75
|
75
|
75
|
||
100
|
100
|
100
|
100
|
Table 3
Completion of table 4 (keypad
method)(step 7):
Input
(“ W.C.)
|
Measured Loop
Current
(DMM, mA)
|
Smart
Tx Pressure (“
W.C.)
|
Error
(“ W.C.)
|
0.00
|
|||
25.00
|
|||
50.00
|
|||
75.00
|
|||
100.00
|
Table
4
Note,
for table 4, pressure is to be calculated based on the mA signal as measured
and indicated by the DMM.
Completion of table 5 (pressure input
source method)(step 9):
Input
(kPa)
|
Measured Loop
Current
(DMM, mA)
|
Smart
Tx Pressure (kPa)
|
Error
(kPa)
|
5.00
|
|||
10.00
|
|||
15.00
|
|||
20.00
|
Table
5
Note,
for table 5, pressure is to be calculated based on the mA signal as measured
and indicated by the DMM.
Reference : NAIT Edmonton CA
0 ความคิดเห็น:
แสดงความคิดเห็น
สมัครสมาชิก ส่งความคิดเห็น [Atom]
<< หน้าแรก