Smart Temperature Transmitter
TTC SMART
TEMPERATURE TRANSMITTER LAB #X
YOKOGAWA YT200
OBJECTIVES
1. Introduce
the Yokogawa YT200 Smart Temperature Transmitter and BT200 Brain Terminal
functions and operations.
2. Calculate
and validate smart temperature transmitter output responses.
3. Perform
a 4-20 mA trim (i.e. "D to A" calibration).
4. Calibrate
the input section (i.e. "A to D" calibration).
THEORY
Smart
transmitters are microprocessor based instruments intended for applications
requiring improved accuracy and remote transmitter communication. These applications incorporate transmitters
installed in inaccessible locations and transmitters requiring frequent range
or calibration changes.
Smart
field communicators are hand held interfaces that permit communication with the
smart transmitters. Communication
includes both sending and receiving data from the transmitter over a
communication link. This link is
actually the 4-20 mA signal wiring on which a digital signal is
superimposed. The communication link to
the transmitter can take place at the transmitter, from the control room, or
from any wiring termination point in the measurement loop.
EQUIPMENT
-
Yokogawa YT200 Smart Temperature Transmitter -
250 Ohm Resistor
- Yokogawa BT200 Brain Terminal -
24 Volt Power Supply
-
Fluke 8060A DMM -
Type J Thermocouple
-
100 PT100D RTD -
Temperature Baths
-
Micromite II Calibrator
PRE-LAB
1.
Explain the difference between a
smart temperature transmitter and a conventional analog temperature
transmitter.
2. Explain what is meant by “configuring” a smart temperature transmitter
versus "calibrating" a smart temperature transmitter.
PROCEDURE
1. Make a proper ice bath. Set the temperature baths for 50°C
and 80°C.
Having exactly the right temperature (baths) is not necessary.
2. Connect the Yokogawa YT200 Smart
Temperature Transmitter to the bench 24 volt power supply. Include in the loop a 250 ohm resistor
(necessary for digital communication), Fluke DMM, and the BT200 Brain Terminal. Note that the BT200 can be connected at any
termination point in the signal loop.
Refer to the drawing shown below:
3. First
turn on the 24 volt power supply for the transmitter, then turn on the BT200
Brain Terminal by pressing the [ON/OFF] key. The brain terminal runs through a self-test,
then comes up in the initial data panel.
From the initial data panel, you can access the main menu panel by
pressing the [F4] key. Please see
pages 4-6 to 4-12 of the BT200 Brain Terminal manual for the basic operations
of the terminal.
To
become familiar with moving around the menu structure of the 275, follow the
procedure as outlined on pages 4-6 to 4-13 of the BT200 Brain Terminal manual, “BASIC OPERATIONS”.
Note that these pages are for connection to a pressure transmitter, but
the menus for the temperature transmitter are quite similar.
4. Configure
the YT200 Smart Temperature Transmitter for the following:
Input Type = type
J thermocouple
Unit = C
Lower Range Value = 0C
Upper Range Value = 80C
Damping Time = 1
second
Display Select = user set
RJC setting = on
Note, all
of the above changes to the configuration are "output-related
information" elements. The communication
block diagram and parameter summary are the only references provided by the manufacturer,
these are on pages 23 to 26 of the YT200 manual.
Note,
don't bother changing the non-output related information at this time... these
elements do not directly affect the transmitter output, so we will ignore this
information for the time being!
5.
Quickly verify the configuration by
measuring the temperature of each bath with a thermometer and the YT200
Temperature Transmitter. Record all required information in table 1. (Note,
reference temperature measurement is the glass thermometer ... don't forget
about the correction factor!)
5. (continued)
Note,
it is possible to display the temperature and transmitter output (as measured
by the transmitter) on the brain terminal display. Go to the main menu panel, then select option
A, “DISPLAY”.
Temperature and transmitter output are updated once every 6 seconds.
Note,
for table 1, temperature is to be calculated based on the mA signal as measured
and indicated by the DMM.
6. It
is possible to set the transmitter to fail up or down via software
configuration. Refer to the block
diagram and parameter summary on pages 24 to 26 of the YT200 manual, then configure
the transmitter for upscale burnout. To verify upscale burnout, simulate
thermocouple burnout by disconnecting one of the thermocouple wires from the
transmitter, then observe the transmitter output signal as indicated by the
DMM. Record your observations
7. Configure
the transmitter for downscale burnout. To verify downscale burnout, simulate
thermocouple burnout by disconnecting one of the thermocouple wires from the
transmitter, then observe the transmitter output signal as indicated by the
DMM. Record your observations
8. Disconnect
the thermocouple from the transmitter, then connect a 3-wire, 100 ohm ice point
platinum RTD (European alpha) to the transmitter. Follow the directions given on page 20 of the
YT200 manual.
9. Configure
the 3044C Smart Temperature Transmitter for a 3-wire RTD. Other information as follows:
Input Type = 100
ohm ice point platinum RTD,
European
alpha, 3-wire
Unit = C
Lower Range Value = 0C
Upper Range Value = 100C
Damping Time = 1.0
seconds
Display Select = user set
Refer
to the directions given in step 4.
10 Quickly verify the configuration by
measuring the temperature of each bath with a thermometer and the YT200
Temperature Transmitter. Record all required information in table 2. (Note,
reference temperature measurement is the glass thermometer ... don't forget
about the correction factor!)
Note,
for table 2, temperature is to be calculated based on the mA signal as measured
and indicated by the DMM.
11. Please
note again that it is possible to set the transmitter to fail up or down via software
configuration. Refer to the block
diagram and parameter summary on pages 24 to 26 of the YT200 manual, then configure
the transmitter for upscale burnout. To verify upscale burnout, simulate RTD
burnout by disconnecting the RTD wires from the transmitter, then observe the
transmitter output signal as indicated by the DMM. Record your observations
12. Configure
the transmitter for downscale burnout. To verify downscale burnout, simulate RTD
burnout by disconnecting the RTD wires from the transmitter, then observe the
transmitter output signal as indicated by the DMM. Record your observations
13. With
Yokogawa Smart Transmitters, it is possible to perform a 4-20 mA trim (i.e.
"digital trim", D/A converter).
If this procedure is to be performed, it is important that the
transmitter output be measured with a very accurate ammeter. We will use the Fluke 8060A to measure the
current output ... however, a more accurate meter should be used!
Prior to performing this
calibration, record the current as indicated by the Fluke at 4 mA, 8 mA, 12 mA,
16 mA and 20 mA. Record your
observations in table 3. Perform this
test by going to the main menu panel, then select option K, “TEST”, then select k10, “OUTPUT %”.
Again, refer to the communication
block diagram and parameter summary on pages 23 to 26 of the YT200 manual.
To do a digital trim, go to the main
menu panel, then select option C, “ADJUST”, then select C10 AND C11, “OUTPUT 4mA” and “OUTPUT 20mA”.
Again, refer to the communication
block diagram and parameter summary on pages 23 to 26 of the YT200 manual.
13. (continued)
After performing the digital trim,
record the current as indicated by the Fluke at 4 mA, 8 mA, 12 mA, 16 mA and 20
mA. Record your observations in table 3.
Perform this test by going to the main menu panel, then select option K, “TEST”, then select k10, “OUTPUT %”.
Again, refer to the communication
block diagram and parameter summary on pages 23 to 26 of the YT200 manual.
14. With
Yokogawa Smart Transmitters, it is also possible to calibrate the input
section of the transmitter (i.e. "sensor trim", A/D converter). If this procedure is to be performed, it is
important that the transmitter input be simulated with a very accurate
device. In this step, we will use
the Micromite II to simulate an RTD input ... however, a more accurate device
should be used!
Disconnect
the 3-wire RTD from the transmitter, then connect the Micromite II to the
transmitter (make the Micromite II look like a 3-wire RTD).
Prior
to performing the sensor trim, ensure that the transmitter is still configured
for a temperature range of 0C to 100C, then
record the temperature as indicated by the brain terminal (go to the main menu
panel, then select option A, “DISPLAY”) when simulating temperatures of 0C, 25C, 50C, 75C and 100C (use
RTD table to determine the resistance values that correspond to these
temperatures). Record your observations
in table 4.
To do the sensor trim, go to the
main menu panel, then select option C, “ADJUST”, then select C20 AND C21, “ZERO ADJ” and “SPAN ADJ”.
Again, refer to the communication
block diagram and parameter summary on pages 23 to 26 of the YT200 manual.
After
performing the sensor trim, record the temperature as indicated by the brain
terminal (go to the main menu panel, then select option A, “DISPLAY”) when simulating temperatures of 0C, 25C, 50C, 75C and 100C (use
RTD table to determine the resistance values that correspond to these
temperatures). Record your observations
in table 4.
15. Now that you have performed a 4-20 mA
trim and a sensor trim, repeat step 11. Record all required information in
table 5. You should find that you now
have less error due to the "trims".
Note,
again, temperature is to be calculated based on the mA signal as measured and
indicated by the DMM.
TTC RESULTS LAB #X
NAME: _______________________________ DATE: __________________
LAB
PARTNER:
_____________________________ CLASS:
_________________
Pre-Lab
Signature: ________________________
Difference between a smart temperature
transmitter and a conventional analog temperature transmitter (pre-lab Q#1):
What
is meant by "configuring" versus "calibrating" (pre-lab
Q#2):
Completion of table 1 (step 5):
Temp
Source
|
Uncorrected
Thermometer Reading (°C)
|
True
Source Temp. (°C)
|
Measured Loop
Current (DMM, mA)
|
Smart Tx
Temp.
(°C)
|
Error
(°C)
|
Ice
bath
|
|
|
|
|
|
50C
bath
|
|
|
|
|
|
80C
bath
|
|
|
|
|
|
Table
1
Note,
for table 1, temperature is to be calculated based on the mA signal as measured
and indicated by the DMM.
Observation
of transmitter output (step 6):
Observation
of transmitter output (step 7):
Completion
of table 2 (step 10):
Temp
Source
|
Uncorrected
Thermometer Reading (°C)
|
True
Source Temp. (°C)
|
Measured Loop
Current (DMM, mA)
|
Smart Tx
Temp.
(°C)
|
Error
(°C)
|
Ice
bath
|
|
|
|
|
|
50C
bath
|
|
|
|
|
|
80C
bath
|
|
|
|
|
|
Table
2
Note,
for table 2, temperature is to be calculated based on the mA signal as measured
and indicated by the DMM.
Observation
of transmitter output (step 11):
Observation
of transmitter output (step 12):
"D to A" calibration (step 13):
Before
|
After
|
||||
Output
Setting (%)
|
Expected
Current (mA)
|
Actual
Current (mA)
|
Output
Setting (%)
|
Expected
Current (mA)
|
Actual
Current (mA)
|
0
|
4
|
|
0
|
4
|
|
25
|
8
|
|
25
|
8
|
|
50
|
12
|
|
50
|
12
|
|
75
|
16
|
|
75
|
16
|
|
100
|
20
|
|
100
|
20
|
|
Table
3
"A to D" calibration (step 14):
Before
|
After
|
||||
Simulated
Input Setting
(°C)
|
Expected
Temp. Display
(°C)
|
Actual
Temp. Display
(°C)
|
Simulated
Input Setting
(°C)
|
Expected
Temp. Display
(°C)
|
Actual
Temp. Display
(°C)
|
0
|
0
|
|
0
|
0
|
|
25
|
25
|
|
25
|
25
|
|
50
|
50
|
|
50
|
50
|
|
75
|
75
|
|
75
|
75
|
|
100
|
100
|
|
100
|
100
|
|
Table
4
Completion
of table 5 (step 15):
Temp
Source
|
Uncorrected
Thermometer Reading (°C)
|
True
Source Temp. (°C)
|
Measured Loop
Current (DMM, mA)
|
Smart Tx
Temp.
(°C)
|
Error
(°C)
|
Ice
bath
|
|
|
|
|
|
50C
bath
|
|
|
|
|
|
80C
bath
|
|
|
|
|
|
Table
5
Note,
for table 5, temperature is to be calculated based on the mA signal as measured
and indicated by the DMM.
Reference NAIT Edmonton CA
0 ความคิดเห็น:
แสดงความคิดเห็น
สมัครสมาชิก ส่งความคิดเห็น [Atom]
<< หน้าแรก